Secutron Products Fire Releasing Control Panels MR-2320 Series Agent Release Control Panel


MR-2320 Series Agent Release Control Panel
MR-2320 Series Agent Release Control Panel
View Full Image


Secutron's MR-2320 is a dual releasing control panel that is field configurable for use on Deluge Sprinkler Systems, Pre-action Sprinkler Systems and Agent Release Systems.

The MR-2320 is equipped with six Class "B" (Style  "B") input circuits and four Class  "B"  (Style "Y") output circuits rated @ 1.7 Amps maximum. (Total of 5 Amps) Optional Class A converter modules are available for both input and output circuits. In addition both internal and external relays are supported by the MR-2320. The relays can be configured for both single and dual hazard applications.



Features

  • Listed to UL 864, 9th edition
  • Field configurable to operate with a Deluge Sprinkler System, a Pre-action Sprinkler System and an Agent Release System
  • Six Class B (Style B) Input Circuits
  • Input Circuits One to Four can be configured as Non-Verified Alarm, Non Latching Supervisory, Latching Supervisory or Agent Release/Water Flow depending on the Mode of Operation selected
  • Input Circuits Five & Six can be configured as Manual Release Input, Abort Input or  Abort/Manual Release Combination Input depending on the Mode of Operation selected
  • Input Circuits can be converted to Class "A" (Style "D") using the MR-2300-A Converter Module
  • Four Class "B" (Style "Y") Output Circuits which can be configured for Silenceable Signal, Non-Silenceable Signal, Silenceable Strobe, Non-Silenceable Strobe or Releasing Circuit (Circuits 3 & 4 Only)
  • Output Circuits can be converted to Class "A" (Style "Z") using the MR-2300-NC4 Converter Module
  • 6 Amp Power Supply
  • 4-wire smoke power 22.3 VDC @ 300ma max.Supervised Aux Power 22.3 VDC @ 500ma max.
  • Aux Power (Unregulated) 24 VDC @ 1.7 Amp max.
  • Relay contacts for Common Alarm (Non Disconnectable), Auxiliary Alarm (Disconnectable), Common Supervisory (can be converted to common alarm if no Supervisory input) and Common Trouble
  • Cross Zone option
  • Counting Zones option
  • Output signals can be configured for Steady (fixed) or Escalating (tone changes as input operation changes)
  • Release Timer 0 to 60 Seconds (5 second increments)
  • Manual Release Delay 0 to 30 Seconds (5 second increments)
  • Soak Timer 0 to 15 Minutes (21 Intervals)
  • Abort Release Timer (Standard UL Type Delay, IRL Type Delay, NYC Type Delay, Local Jurisdiction Delay)
  • Special Releasing Power Supply and Release Activation Considerations preventing false dumps
  • Configurable to perform two hazard areas
  • Simple panel programming through 14 Pre-Configured Modes of Operations